July 2025 brought sustained afternoon intake temperatures above 33°C at three client halls we visited within 40 km of Gumi. We logged parallel nameplate 0.06–0.09 PH/s units under normal operating policies—no intentional throttling.

Method

  • Intake thermocouples at louver face
  • Rear exhaust probe 30 cm from unit outlet
  • Hash logging via pool API at five-minute intervals
  • Ambient outdoor temperature from KMA station for correlation

Findings

SiteIntake peakAvg hash derate vs spring baseline
North Gumi warehouse34.1°C−12%
West Gumi industrial unit32.8°C−8%
Converted storage hall35.2°C−15%

Derating correlated more strongly with intake than outdoor temperature. One site with shaded intake maintained −6% despite hotter outdoor readings.

Operator takeaway

Spec sheets citing 0.07 PH/s at 25°C ambient understate summer output for unshaded louvers facing afternoon sun. Budget hash forecasts using July intake, not spring commissioning data.

Mitigation we documented

Operators who saw −6% or better had:

  • Intake louvers on north-facing walls or shaded baffles
  • Minimum 1.5 m separation between exhaust outlet and intake path
  • Filters cleaned within the prior 30 days